Power Analyse JANITZA UMG 104

- Measurement in IT, TN and TT systems,
- 4 voltage measurement inputs
- 4 current measurement inputs,
- Continuous scanning of the voltage and current measurement inputs,
- Energy measurement, measurement uncertainty class 0.5 for ../5A current transformers,
- Energy measurement, measurement uncertainty class 1 for ../1A current transformers,
- Registers more than 800 measured values (readings),
- 2 digital inputs,
- 2 digital outputs,
- Temperature measurement input,
- LC display, backlight (optional),
- Profibus DPV0 (optional),
- RS485 (modbus RTU),
- RS232,
- Suitable for installation in distribution boards,
- Suitable for measurements in networks with frequency inverters.

Marcă:   Janitza
Unitate:   pcs
Cod:   OTH-JAN-POWERA-104
Garanție:   2 an

 The UMG104 is intended to be used for the measurement and calculation of electrical variables such as voltage, current, energy, work, harmonic components, etc. in building installations, at distribution boards, circuitbreakers and busbar trunking systems. Measuring-circuit voltages and currents must originate from the same system. The UMG104 is permanently installed in control cabinets or small distribution boards. It can be installed in any position. The measurement results can be displayed, stored and read out via serial interfaces and further processed. The voltage measurement inputs are designed for measurements in low-voltage systems in which rated voltages up to 300 V conductor to earth and surge voltages of overvoltage category III can occur. The current measurement inputs of the UMG104 are connected via external ../1A or ../5A current transformers. Mains failure detection The mains failure detection takes place via the voltage measurement inputs. The selection of voltage measurement inputs can be configured using the GridVis software. Mains failure stored energy time The UMG104 bridges the following mains failures at the auxiliary voltage input: Mains voltage Stored energy time 230V AC max 80ms 

Janitza 104-Manual-PDF
3677_JANITZA-BHB-UMG104-EN.PDF
General information
Net weight 350g
Device dimensions approx l=107.5 mm, b=90 mm, h=82 mm (according to DIN 43871:1992)
Housing flammability class  UL94V-0
Installed position  any
Fixing/mounting 35 mm top hat rail (according to IEC/EN 60999-1, DIN EN 50022)
Battery  Type VARTA CR2032, 3 V, Li-Mn
Backlight lifetime (optional)  40000h (50% of initial brightness)
Ambient conditions during operation
The UMG104 is intended for weather-protected, stationary use. The UMG104 fulfils the use conditions according to DIN IEC 60721-3-3.
Operating temperature range -10°C. +55°C
Relative humidity  5 to 95 %, (at +25 °C) without condensation
Degree of pollution 2
Operating altitude 0 .. 2000 m above sea level
Installed position  any
Ventilation Forced ventilation is not required.
Transport and storage 
The following information applies to devices which are transported or stored in the original packaging.
Free fall 1m
Temperature   -20°C to +70°C
Power supply voltage
The power supply voltage must be connected to the UMG104 via a UL listed fuse.
Line circuit breaker 6A, Typ C (approved to UL / IEC)
Cylindrical fuses  0.6A, tripping characteristics M (medium time lag)
Cylindrical fuses 0.75A, tripping characteristics F (fast acting)
Option 230V:
Nominal range 95V .. 240V (50/60 Hz) or DC 135V .. 340V
Operating range +-10% of nominal range
Installation overvoltage category 300V CATIII
Power consumption max 3.2W, max 9VA
Option 90V
Nominal range 50V .. 110V (50/60 Hz) or DC 50V .. 155V
Operating range +-10% of nominal range
Installation overvoltage category 300V CATII
Power consumption max 3.2W, max 9VA
Option 24V
Nominal range 20V .. 50V (50/60 Hz) or DC 20V .. 70V
Operating range +-10% of nominal range
Installation overvoltage category 300V CATII
Power consumption max 5W, max 8VA
Connectable conductors
Only one conductor may be connected per terminal connection!
Solid core, multi-core, flexible core  0.08 - 2,5 mm2, AWG 28 - 12
Pin-end connector, wire end ferrules 1.5 mm2, AWG 16
Protection class
Class II according to IEC 60536 (VDE 0106, Part 1), i.e. a PE terminal is not required! 
Protection against ingress of solid foreign bodies and water IP20 according to EN 60529 September 2000, IEC 60529:1989
Inputs and outputs
2 digital inputs
Pulse input (S0)
Maximum counting frequency 20 Hz
Switching input
Response time (Jasic program) 200 ms
Input signal applied 18V. 28 V DC (typically 4 mA)
Input signal not applied  0 .. 5 V DC, current less than 0.5 mA
2 digital outputs, semi-conductor relay, not short-circuit proof.
Switching voltage  max 60 V DC, 30 V AC
Switching current  max 50 mAeff AC/DC
Response time (Jasic program) 200 ms
Output of voltage dips  20 ms
Output of voltage overranges 20 ms
Pulse output (operating pulses) max 20 Hz
Cable length up to 30 m greater than 30m shielded
Connectable conductors
Solid core, multi-core, flexible core 0.08 - 1.5 mm2 
Pin-end connector, wire end ferrules 1 mm2, only one conductor may connected per terminal connection!
Temperature measurement input 
Update time approx 200 ms
Connectable sensors PT100, PT1000, KTY83, KTY84
Total burden (sensor + cable) max 4 kohm
Sensor type Temperature range Resistance range Measurement uncertainty
KTY83 -55 ° .. +175 °C 500 ohm .. 2.6 kohm  ± 1.5% rng
KTY84 -40 ° .. +300 °C 350 ohm .. 2.6 kohm ± 1.5% rng
PT100 99 ° .. +500 °C 60 ohm .. 180 ohm ± 1.5% rng
PT1000 -99 ° .. +500 °C 600 ohm .. 1,8 kohm ± 1.5% rng
Cable length up to 30 m unshielded,  greater than 30 m shielded
Connectable conductors:
Solid core, multi-core, flexible core  0.08 - 1.5 mm2
Pin-end connector, wire end ferrules  1 mm2, only one conductor may be connected per terminal connection!
Interfaces
RS232 5 pin screw-type terminals
   Protocol Modbus RTU/slave
   Transfer rate  9600 bps, 19.2 kbps, 38.4 kbps, 115.2 kbps
RS485 2 pin screw-type terminals
   Protocol, modbus RTU Modbus RTU/slave
   Transfer rate 9.6 kbps, 19.2 kbps, 38.4 kbps, 57.6 kbps, 115.2 kbps, 921.6 kbps
RS485 (optional) Connector, SUB D 9 pin
   Protocol, profibus (optional) Profibus DP/V0 according to EN 50170
   Transfer rate  EN 50170 Transfer rate : 9.6 kbaud up to 12 Mbaud